1 60-2285—7R4795AFlame SafeguardPrimary ControlsThe R4795A Protectorelay™ Primary Controlprovides solid state electronic flame safeguardprotection for
60-2285—7 10R4795ACHECKOUTCAUTIONDo not manually push in the relays.4. Check that the pilot is lit and relay 2K is pulled in.5. Open the manual main b
11 60-2285—7R4795AOPERATION • TROUBLESHOOTINGOperationNORMAL OPERATION (REFER TO FIG. 2 AND 3.)Call for Heat (Limit SwitchClosed)Terminal 1 energized.
60-2285—7 12R4795ATROUBLESHOOTINGF. Pilot lights and relay 2K pulls in but the main burnerdoes not light.G. Relay 2K remains in after flame is extingu
13 60-2285—7R4795ATROUBLESHOOTING • SERVICE(3) Remove any flame simulating condition suchas false light.(4) Note that any change made in the detector
60-2285—7 14R4795ASERVICEIMPORTANT:1. Do not clean contacts unless absolutely necessary.2. Use only Honeywell Contact Cleaner part no. 132569.Do not u
15 60-2285—7
Home and Building Control Home and Building ControlHoneywell Inc. Honeywell Limited—Honeywell Limitée1985 Douglas Drive North 740 Ellesmere RoadGolden
60-2285—7 2R4795ASPECIFICATIONS • ORDERING INFORMATIONSpecificationsR4795A Flame Safeguard Primary Control recycles onceafter flame failure to try t
3 60-2285—7R4795ASPECIFICATIONSTERMINAL RATINGS:Terminal Load Rating3 Pilot Valve 125 VA pilot duty.Intermittent Ignitiona360 VA.4 Interrupted Ignitio
60-2285—7 4R4795AINSTALLATIONInstallationVibrationDo not install the R4795A where it could be subject toexcessive vibration. Vibration shortens the li
5 60-2285—7R4795AINSTALLATIONIMPORTANT: Do not run high voltage ignition trans-former wires in the same conduit with the flamedetector wiring.5. For i
60-2285—7 6R4795AINSTALLATIONReplacing RA890E,F,G with R4795A1. Disconnect all wires from terminal 1, and splice withsolderless connector. (If RA890 h
7 60-2285—7R4795AINSTALLATIONFig. 6—Flame detector wiring.M8686BLUEWHITEFGC7027, C7035, OR C7044ULTRAVIOLET FLAME DETECTORBLUEYELLOWBLACKBLACKFGC7012
60-2285—7 8R4795ACHECKOUTCheckoutFig. 10—Internal view showing amplifier andtest jack for flame current test.CAUTIONUse extreme care while testing the
9 60-2285—7R4795ACHECKOUT2. The flame current is at least two microamperes forR7289A Rectification Amplifier (color-coded green), or atleast 1.5 micro