PRODUCT DATA
63- 2567- 3
® U.S. Registered Trademark
Copyright © 2000 Honeywell • All Rights Reserved
N314
ML4125, ML4135, ML8125, ML8135
Fast-Acting, Two-Position Actuators
FOR HEATING, VENTILATION AND
AIR-CONDITIONING APPLICATIONS
APPLICATION
The ML4125, ML4135, ML8125 and ML8135 Fast-Acting,
Two-Position Actuators are spring return direct coupled
actuators (DCA) with an integral junction box for on/off
damper control. The actuator accepts an on/off signal from
a single-pole, single-throw (spst) controller. Models are
available with clockwise (cw) or counterclockwise (ccw)
spring return and are designed for heating, ventilation, and
air-conditioning (HVAC) applications.
IMPORTANT
This actuator is not to be used in fire/smoke
applications requiring UL555/555S approval.
FEATURES
Integral spring return.
-40 to 130°F (-40 to 54°C) operating temperature range.
No audible noise during holding.
Electronic circuitry provides efficient operation while
eliminating the need for limit switches.
Ninety-five degree angle of rotation.
Die-cast aluminum housing.
Housing design allows flush mounting to damper.
Integral junction box with three conduit openings
eliminates need for separate wiring box.
Direct mounting to 3/8 or 1/2 in. round or square shaft.
ML4125, ML8125
100 lb-in. (11.3 N•m) minimum driving torque.
25 to 40 second drive timing (load dependant).
Models available for 24, 120, and 230 Vac.
ML4135, ML8135
40 lb-in. (4.5 N•m) minimum driving torque.
20 to 25 second drive timing (load dependant).
Models available for 24 and 120 Vac.
APPLICABLE LITERATURE
Motor/Actuator Selection Guide
for Damper Applications 63-8419
Engineering Manual of Automatic Control
(also called The Gray Manual) 77-1100
Direct Coupled Actuator
Quick Selection Guide 63-8553
Damper Torque Calculator 63-8437
Contents
Application ........................................................................ 1
Features ........................................................................... 1
Specifications ................................................................... 2
Ordering Information ........................................................ 2
Installation ........................................................................ 4
Operation .......................................................................... 6
Checkout .......................................................................... 6
Seitenansicht 0
1 2 3 4 5 6 7 8

Inhaltsverzeichnis

Seite 1 - FOR HEATING, VENTILATION AND

PRODUCT DATA63- 2567- 3® U.S. Registered TrademarkCopyright © 2000 Honeywell • All Rights Reserved N314ML4125, ML4135, ML8125, ML8135Fast-Acting, Two

Seite 2 - SPECIFICATIONS

ML4125, ML4135, ML8125, ML8135 FAST-ACTING, TWO-POSITION ACTUATORS63-2567—32ORDERING INFORMATIONWhen purchasing replacement and modernization products

Seite 3 - 3 63-2567—3

ML4125, ML4135, ML8125, ML8135 FAST-ACTING, TWO-POSITION ACTUATORS3 63-2567—3Mounting:3/8 in. (10 mm) to 1/2 in. (13 mm) square or round damper shafts

Seite 4 - INSTALLATION

ML4125, ML4135, ML8125, ML8135 FAST-ACTING, TWO-POSITION ACTUATORS63-2567—34INSTALLATIONWhen Installing this Product...1.Read these instructions caref

Seite 5 - Installation

ML4125, ML4135, ML8125, ML8135 FAST-ACTING, TWO-POSITION ACTUATORS5 63-2567—3InstallationCAUTIONDevice Malfunction Hazard.Improper set screw tightenin

Seite 6 - CHECKOUT

ML4125, ML4135, ML8125, ML8135 FAST-ACTING, TWO-POSITION ACTUATORS63-2567—36OPERATIONThe actuators are operated by an spst two-position controller. Wh

Seite 7 - 7 63-2567—3

ML4125, ML4135, ML8125, ML8135 FAST-ACTING, TWO-POSITION ACTUATORS7 63-2567—3D MontageanweisungF Instructions d’InstallationI Istruzioni per I’Install

Seite 8

63-2567—3 B.B. Rev. 7-00 www.honeywell.comPrinted in U.S.A. on recycled paper containing at least 10% post-consumer paper fibers.ML4125, ML4135,

Kommentare zu diesen Handbüchern

Keine Kommentare