SMARTBOX™ Controller for HONEYWELL™ Wind Turbine WT6500 Owner’s Manual - Rev14
SMARTBOX Installation
AC Output Over-current Protection
The NEC/CEC requires the AC output circuit to be protected with a device rated for
125%oftheratingofthecircuit.TheAC-ratedfuseorcircuitbreakerbetweenthe
battery and the SMARTBOX™ Controller must have a maximum size of 15A (the
maximum current rating of the SMARTBOX™ Controller).
SHOCK OR FIRE HAZARD
A maximum of a 15amp over-current protection must be
installed to protect the SMARTBOX™ Controller from
short circuits and to provide a means of disconnecting the
SMARTBOX™ Controller. Failure to follow this warning
may result in death, personal injury or property damage.
AC IN
L1 N GND
AC OUTPUT
TO SUB SWITCH
BOARD
SINGLE PHASE
120V 15AMP
L1 N GND
AC INPUT
FROM MAIN SWITCH
BOARD
SINGLE PHASE
120V 15AMP
(2) #12 THWN-2
+ #6 GND
¾” CONDUIT
(2) #12 THWN-2
+ #6 GND
¾” CONDUIT
15 AMP FUSE OR
BREAKER
Turbine SMARTBOX™ Controller
Figure 2.11 AC Circuit Diagram