T874G Thermostats
and Q674F,J Subbases
for Heat Pump Systems
J.H. • Rev. 7-94 • • ©Honeywell Inc. 1994 • Form Number 69-0435—10
TRADELINE
®
TABLE 1—THERMOSTAT/SUBBASE SPECIFICATIONS.
Application
The T874G Thermostats and Q674F,J Subbases pro-
vide 24 to 30 Vac control of 2-stage heating and 1-stage cool-
ing heat pump systems with automatic changeover. Stage 1
heat and cool anticipation is fixed voltage type; stage 2 heat
anticipation is adjustable (except as noted). See Table 1 for
specific T874G/Q674F,J combinations and specifications.
Installation Instructions for the Trained Service Technician.
Thermostat/
Subbase
Thermostat/
Subbase
Model LED
Switching
See
Package Numbers Indication
System Fan Changeover Comments
Fig.
Y594G1252 T874G1246/
Q674F1212
AUX.HT.,
EM.HT.
a
EM.HT.-OFF-
HEAT-AUTO-
COOL
AUTO-
ON
AUTO,
COOL
TRADELINE
®
5
T874G1246/
Q674F1410
AUX.HT.,
EM.HT.
a
EM.HT.
b
-OFF-
HEAT-AUTO-
COOL
AUTO-
ON
AUTO,
COOL
Separate W1 and Y1
terminals; TRADELINE
®
subbase.
6
Y594G1419 T874G1642/
Q674F1444
AUX.HT.,
EM.HT.,
CHECK
OFF-EM.HT.-
HEAT-AUTO-
COOL
AUTO-
ON
AUTO,
HEAT OR
COOL
SUPER TRADELINE
®
;
includes factory-installed
jumper across W1 and Y1;
fixed stage 2 heat anticipation.
7
Y594G1476
c
T874G1741/
Q674F1477
Isolated CHECK LED
includes jumper for connecting
X2 terminal to X or R for
power.
Y594G1534
d
T874G1824/
Q674F1477
Y594G1526 T874G1626/
Q674F1436
AUX.HT.,
EM.HT.
OFF-EM.HT.-
HEAT-AUTO-
COOL
AUTO-
ON
AUTO,
HEAT
TRADELINE
®
8
T874D1165
or
T874E1016/
Q674F1543
(RED)
e
OFF-EM.HT.-
HEAT-AUTO-
COOL
AUTO-
ON
AUTO TRADELINE
®
subbase; exact
replacement for York model
no. 2TB04700524. Thermostat
not included; order separately.
9
Y594G1567 T874G1865/
Q674J1209
EM.HT. EM.HT.-
AUTO-OFF
AUTO-
ON
AUTO,
COOL
TRADELINE
®
; exact
replacement for York model
nos. 2TH11702424 and
6TH11702424.
10
Y594G1575
c
T874G1873/
Q674J1225
EM.HT. EM.HT.-
AUTO-OFF
AUTO-
ON
AUTO,
COOL
TRADELINE
®
; exact
replacement for York model
nos. 2TH11702424 and
6TH11702424.
10
Y594G1633 T874G1972/
Q674F1584
AUX.HT.,
EM.HT.
OFF-EM.HT.-
HEAT-AUTO-
COOL
AUTO-
ON
AUTO,
HEAT OR
COOL
TRADELINE
®
11
a
EM.HT. also shows compressor malfunction.
b
When switch is in EM. HT. position, the emergency heat will operate continuously until system switch is moved to another position.
c
Thermostat is white and subbase is gray.
d
Sold only in Australia; degrees C.
e
LED indicator is not labeled but may be connected per user's requirements. See Fig. 9.
M3375
Seitenansicht 0
1 2 3 4 5 6 ... 11 12

Inhaltsverzeichnis

Seite 1 - T874G Thermostats

T874G Thermostatsand Q674F,J Subbasesfor Heat Pump SystemsJ.H. • Rev. 7-94 • • ©Honeywell Inc. 1994 • Form Number 69-0435—10TRADELINE®T

Seite 2 - Operation

69-0435—10 10

Seite 4 - 69-0435—10 4

Home and Building Control Home and Building ControlHoneywell Honeywell Limited—Honeywell Limitée1985 Douglas Drive North 35 Dynamic DriveGolden Valley

Seite 5 - 5 69-0435—10

69-0435—10 2IMPORTANT: Thermostats are calibrated at the factory byusing subbases mounted at true level. Inaccurate sub-base leveling will cause therm

Seite 6 - 69-0435—10 6

3 69-0435—10Fig. 2—Installation of Q674 Subbase on wall.WIRES THROUGHWALL OPENINGWALL WALLANCHORS(2)SUBBASEMOUNTINGHOLESMOUNTINGSCREWS (2)M926Fig. 3—S

Seite 7

69-0435—10 4Fig. 5—Internal schematic and typical wiring diagram for Y594G1252 (T874G1246/Q674F1212); autochangeover in cooling.H2FALLL1 (HOT)L21RW3W2

Seite 8 - 50 60 70 80

5 69-0435—10Fig. 7—Internal schematic and typical wiring diagram for Y594G1419 (T874G1642/Q674F1444),Y594G1476 (T874G1741/Q674F1477) and Y594G1534 (T8

Seite 9 - Calibration

69-0435—10 6Fig. 8—Internal schematic and typical wiring diagram for Y594G1526 (T874G1626/Q674F1436); autochangeover in heating.M1592A(HOT) L1 L21LAC

Seite 10 - 69-0435—10 10

7 69-0435—10Fig. 10—Internal schematic and typical wiring diagram for Y594G1567 (T874G1865/Q674J1209) andY594G1575 (T874G1873/Q674J1225); auto changeo

Seite 11 - 11 69-0435—10

69-0435—10 8MOUNTING THE THERMOSTAT1. Remove the thermostat cover by pulling the bot-tom edge of the cover away from the base until it snapsfree of th

Seite 12

9 69-0435—10CheckoutHEATINGMove the system switch on the Q674 Subbase toHEAT. Move the heating set point lever on the T874Thermostat about 10° F [6° C