Honeywell
M9484 AND M9494 MODUTROL MOTORS ARE LOW
VOLTAGE, REVERSING PROPORTIONAL CONTROL
ACTUATORS FOR VALVES, DAMPERS AND AUXIL-
IARY EQUIPMENT. THEY ARE ESPECIALLY DE-
SIGNED
FORCOMMERCIALOR
INDUSTRIALOILOR
GAS BURNER CONTROL SYSTEMS.
•i Replace M941 motors.
0
Oil immersed motor and gear train for reliable per-
formance and long life.
0
Wiring box provides NEMA 3 weather protection.
0
Actuator motor and circuitry operate from 24 volts
AC. Models available with factory installed transformer,
or internal transformer can be field added.
Cl
Quick-connect terminals standard
-
screw terminal
adapter available.
Cl
Adapter bracket for matching shaft height of older
motors is standard with replacement motors.
0
Field adjustable stroke (90” to 160’) models avail-
able.
q
Nominal timing of 30 seconds for 90” and 60 sec-
onds for
160”
stroke is standard. Other timings are
available.
0
Die-cast magnesium housing.
q Available accessories include valve and damper
linkages, explosion proof housing, and auxiliary
,
switches.
0
Field addable interface modules can be mounted in
wiring box to upgrade actuator to Series 70 (electronic)
control.
•i
Models available with tapped output shaft.
0
M9481,
M9484 rated for 150 lb.-in. torque at stan-
dard timings.
cl
M9491,
M9494 rated for 300 lb.-in. torque at 2 or 4
minute timings for
160“
stroke.
S.M.
Form Number 63-2195-l
Rev. 11-90
@Honeywell Inc. 1990
Seitenansicht 0
1 2 3 4 5 6 ... 11 12

Inhaltsverzeichnis

Seite 1 - Honeywell

HoneywellM9484 AND M9494 MODUTROL MOTORS ARE LOWVOLTAGE, REVERSING PROPORTIONAL CONTROLACTUATORS FOR VALVES, DAMPERS AND AUXIL-IARY EQUIPMENT. THEY AR

Seite 2 - STANDARD MODELS

IMPORTANTSet cams by moving top of screwdriver only. Press-ing screwdriver against sides of cam slots couldcause damage to motor end switches.4. Inser

Seite 3

n1POWER SUPPLY. PROVlDE DISCONNECT MEANS AND OVERLOADPROTECTION AS REQUIRED.n2 TRANSFORMER MAY BE INTERNAL OR EXTERNAL TO MOTOR.EJ74CSPDT SWITCHOR SER

Seite 4 - 1-UIMtNSIUNS

4074EED RESISTOR SELECTION CHART FOR4-20 mAMIINIMUMOUTPUTVOLTAGEREQUIREDMOTORS (Vdc)bRESISTOR (A)(Ohms) Part No.1 1.7 237 80213QCDHA2 2.0 150 802139BF

Seite 5 - NON SPRING RETURN MOTORS

STANDARD MODELScontrol Type T TTLix Letter94 is Series 90~~ IPower Rating8 is high torque150 lb.-in. atstandard timing9 is high torque300 lb.-in.at2 o

Seite 6

AUXILIARY SWITCH RATINGS (amperes):M94XXE has 1 spdt switch.M94XXF has 2 spdt switches.ONE CONTACT a 120v 240vFull Load 7.2 3.6Locked Rotor 43.2 21.6a

Seite 7

f--- 5.37 [136]ADAPTERBRACKETFIG. 1-UIMtNSIUNS INIn.NOTE: M9481, M9491 do not have auxiliary shaft. All other dimensions are the same.LOCATIONinstall

Seite 8

NON SPRING RETURN MOTORSE373CFIG. 2-LIMITS OF MOTOR ROTATION.ADAPTER BRACKETThe220738A Adaptor Bracket, positioned between themotor and the equipment,

Seite 9 - MOVE SCREWDRIVER

Y BOLTS PROVIDED (4)WIRING BOXMOTORMACHINE SCREWS OR BOLTS.LTS SECURING BRACKET TO LINKAGE.M 31% TIGHTEN AFTER SECURING MOTOR TO THE BRACKET USING FOU

Seite 10

CLOSE LIMITDIRECTION OF MOTOR TRAVEL AS VIEWED FROM POWER END.& CONNECT 24V POWER TO Tl-T2 TERMINALS ONLY. DO NOT CONNECTPOWER SUPPLY TO CONTROLLE

Seite 11 - DOTTED LINE CONNECTION

AUXILIARY SWITCH CONNECTIONSsupplies to de-energize theThe M9484E has 1 internal auxiliary switch. The switchwires are color-coded as follows: solid y

Seite 12 - QUALITY IS KEY

MOVE SCREWDRIVER AT TOPONLY TO ADJUST CAM:l/8 IN. STRAIGHT BLADESCREWDRIVEROUTER STROKE OUTER CAMADJUST CAMSRY SWITCH CAMSA1 POWER SUPPLY. PROVIDE DIS

Kommentare zu diesen Handbüchern

Keine Kommentare