PRODUCT DATA
® U.S. Registered Trademark
© 2004 Honeywell International Inc.
All Rights Reserved
71-2429—2
L404F,T,V
PressureTrol
®
Controllers
APPLICATION
L404F PressureTrol
®
Controllers provide operating control
with automatic limit protection for pressure systems of up to
2070 kPa, or 300 psi.
L404T,V PressureTrol® Controllers are for use on oil burner
systems for pressures up to 1035 kPa or 150 psi.
FEATURES
Models available in a series of control ranges, and
pressure scales in kPa and psi.
All models automatically reset and have an adjustable
differential.
Models have snap switch to open or close a circuit on
a pressure rise.
Case has a clear plastic cover so setpoints can be
observed.
1/4 inch—18 NPT connection for pipe on diaphragm
assembly.
Ground screw terminal.
L404F:
Controllers may be used with steam, air, or
noncombustible gases, or fluids noncorrosive to the
pressure sensing element.
L404T:
High pressure limits, break a circuit on oil pressure
rise above setpoint.
L404V:
Low pressure limits, makes a circuit on oil pressure
rise above setpoint.
Contents
Application ........................................................................ 1
Features ........................................................................... 1
Specifications ................................................................... 2
Ordering Information ........................................................ 2
Installation ........................................................................ 3
Settings and Adjustments ................................................. 6
Checkout .......................................................................... 7
Seitenansicht 0
1 2 3 4 5 6 7 8

Inhaltsverzeichnis

Seite 1 - Controllers

PRODUCT DATA® U.S. Registered Trademark© 2004 Honeywell International Inc.All Rights Reserved 71-2429—2L404F,T,VPressureTrol® ControllersAPPLICATIONL4

Seite 2 - SPECIFICATIONS

L404F,T,V PRESSURETROL® CONTROLLERS71-2429—2 2ORDERING INFORMATIONWhen purchasing replacement and modernization products from your TRADELINE® wholesal

Seite 3 - INSTALLATION

L404F,T,V PRESSURETROL® CONTROLLERS3 71-2429—2Table 2. Conversion Table.Table 3. Switch Ratings (Amperes).Pressure Sensing Element: Stainless steel di

Seite 4 - Location and Mounting (L404F)

L404F,T,V PRESSURETROL® CONTROLLERS71-2429—2 4IMPORTANTWhen making pipe connections, use pipe dope sparingly to seal the joints; any excess dope may c

Seite 5 - Using with Preheated Oil

L404F,T,V PRESSURETROL® CONTROLLERS5 71-2429—2Fig. 4. Mounting an oil pressure controller directly on the main pipe.Using with Preheated OilWhen used

Seite 6 - SETTINGS AND ADJUSTMENTS

L404F,T,V PRESSURETROL® CONTROLLERS71-2429—2 6Fig. 8. L404T,V terminal blocks and internal schematics.Fig. 9. Hookup of an oil pressure controller use

Seite 7 - CHECKOUT

L404F,T,V PRESSURETROL® CONTROLLERS7 71-2429—2CHECKOUTAfter the controller has been installed, wired and adjusted, it should be tested with the system

Seite 8

71-2429—2 G.R. Rev. 09-04 www.honeywell.comAutomation and Control SolutionsHoneywell International Inc. Honeywell Limited-Honeywell Limitée1985 Do