Fire Alarm Control Panel MS-2 & MS-4MS-2E & MS-4EPN: 51512:E ECN 05-040Document #5151201/18/05 Revision:E

Seite 2 - Fire Alarm System Limitations

Product Description Product Features10 MS-2/MS-4 PN 51512:E 01/18/05SECTION 1 Product DescriptionThe MS-2 is a two zone FACP (Fire Alarm Control Pa

Seite 3 - Installation Precautions

Product Features Product DescriptionMS-2/MS-4 PN 51512:E 01/18/05 11• Control Buttons ACK (Acknowledge) Alarm Silence Reset Walktest Zone Enab

Seite 4

Product Description Specifications12 MS-2/MS-4 PN 51512:E 01/18/051.2 SpecificationsAC Power - TB8MS-2/MS-4: 120 VAC, 50/60 Hz, 2.3 ampsMS-2E/MS-4

Seite 5 - Table of Contents

Controls and Indicators Product DescriptionMS-2/MS-4 PN 51512:E 01/18/05 131.3 Controls and IndicatorsFront Panel Membrane Buttons• Acknowledge• A

Seite 6

Product Description Circuits14 MS-2/MS-4 PN 51512:E 01/18/05Local Piezo SounderA piezo sounder provides separate and distinct sounds for alarm, tro

Seite 7

Optional Modules and Accessories Product DescriptionMS-2/MS-4 PN 51512:E 01/18/05 151.6 Optional Modules and AccessoriesCAC-4 Class A Converter Mo

Seite 8

Product Description Optional Modules and Accessories16 MS-2/MS-4 PN 51512:E 01/18/05Battery BoxThe Fire•Lite BB-17F battery box may be used to hous

Seite 9 - MS-4(E) Main Circuit Board

Backbox Mounting InstallationMS-2/MS-4 PN 51512:E 01/18/05 17SECTION 2 InstallationThe cabinet can be surface mounted or semi-flush mounted using t

Seite 10 - Product Description

Installation Backbox Mounting18 MS-2/MS-4 PN 51512:E 01/18/05When batteries larger than 7 Amp Hour, up to 18 Amp Hour, are being used, the BB-17F b

Seite 11

Operating Power InstallationMS-2/MS-4 PN 51512:E 01/18/05 192.2 Operating PowerWARNING: Several different sources of power can be connected to thi

Seite 12 - 1.2 Specifications

PrecauLarge.PMD 01/10/2005An automatic fire alarm system–typically made up of smokedetectors, heat detectors, manual pull stations, audible warn-in

Seite 13 - 1.3 Controls and Indicators

Installation Input Circuits20 MS-2/MS-4 PN 51512:E 01/18/052.3 Input CircuitsThe MS-2 has two IDCs (Initiating Device Circuits) and the MS-4 has f

Seite 14 - 1.5 Components

Input Circuits InstallationMS-2/MS-4 PN 51512:E 01/18/05 21Combination Waterflow/Supervisory ZoneA combination Waterflow/Supervisory circuit allows

Seite 15

Installation Output Circuits22 MS-2/MS-4 PN 51512:E 01/18/052.4 Output Circuits2.4.1 Notification Appliance CircuitsThe MS-2 provides one Style Y

Seite 16

Output Circuits InstallationMS-2/MS-4 PN 51512:E 01/18/05 232.4.2 Special Application DC Power Output ConnectionsResettable 24 VDC special applica

Seite 17 - 2.1 Backbox Mounting

Installation Power-limited Wiring Requirements24 MS-2/MS-4 PN 51512:E 01/18/052.5 Power-limited Wiring RequirementsPower-limited and nonpower-limi

Seite 18

Installation of Optional Modules InstallationMS-2/MS-4 PN 51512:E 01/18/05 252.6 Installation of Optional ModulesCAUTION: Remove all power (AC and

Seite 19 - 2.2 Operating Power

Installation Installation of Optional Modules26 MS-2/MS-4 PN 51512:E 01/18/052.6.1.2 Wiring NACs and IDCs for Class AWire the Style Z (Class A) No

Seite 20 - 2.3 Input Circuits

Installation of Optional Modules InstallationMS-2/MS-4 PN 51512:E 01/18/05 272.6.2 4XTMF, 4XLMF and 4XZMF Option ModulesMS-4: The 4XLMF LED Inter

Seite 21 - ZONE 3 ZONE 4

Installation Installation of Optional Modules28 MS-2/MS-4 PN 51512:E 01/18/052.6.2.1 4XTMF Transmitter Module InstallationThe 4XTMF provides a sup

Seite 22 - 2.4 Output Circuits

Installation of Optional Modules InstallationMS-2/MS-4 PN 51512:E 01/18/05 292.6.2.2 4XZMF Zone Relay Module (MS-4 only)The 4XZMF provides four zo

Seite 23 - 2.4.3 Relays

PrecauLarge.PMD 01/10/2005WARNING - Several different sources of power can be con-nected to the fire alarm control panel. Disconnect all sourcesof

Seite 24 - + - +

Installation Installation of Optional Modules30 MS-2/MS-4 PN 51512:E 01/18/052.6.2.3 4XLMF LED Interface Module (MS-4 only)The 4XLMF supports the

Seite 25 - + - +

Installation of Optional Modules Program Options via DIP SwitchMS-2/MS-4 PN 51512:E 01/18/05 31SECTION 3 Program Options via DIP SwitchThis section

Seite 26

Program Options via DIP Switch DIP Switch Settings32 MS-2/MS-4 PN 51512:E 01/18/053.1 DIP Switch SettingsThe following tables list the programmabl

Seite 27

DIP Switch Settings Program Options via DIP SwitchMS-2/MS-4 PN 51512:E 01/18/05 33Table 3.2 MS-4 DIP Switch SettingsSwitch Number DIP Switch Numbe

Seite 28 - 4xtmf.cdr

Program Options via DIP Switch DIP Switch Settings34 MS-2/MS-4 PN 51512:E 01/18/053.1.1 SW1 DIP Switch Settings3.1.1.1 Silence InhibitSwitch 1, p

Seite 29 - 4xzma.cdr

DIP Switch Settings Program Options via DIP SwitchMS-2/MS-4 PN 51512:E 01/18/05 353.1.2 SW2 DIP Switch Settings3.1.2.1 IDC1 Verification (MS-4 o

Seite 30 - 4xlma.cdr

Program Options via DIP Switch DIP Switch Settings36 MS-2/MS-4 PN 51512:E 01/18/053.1.2.5 IDC2 Verification for MS-2 or IDC3 Verification for MS-4

Seite 31 - 12345678

DIP Switch Settings Program Options via DIP SwitchMS-2/MS-4 PN 51512:E 01/18/05 373.1.3.5 Strobe SynchronizationSwitches 5 and 6 are used to progr

Seite 32 - 3.1 DIP Switch Settings

Operating Instructions Switch Functions in Normal Mode38 MS-2/MS-4 PN 51512:E 01/18/05SECTION 4 Operating InstructionsThe MS-2 and MS-4 have two mo

Seite 33

Walktest Operating InstructionsMS-2/MS-4 PN 51512:E 01/18/05 394.1.5 WalktestThe Walktest button, which is located on the FACP membrane switch pan

Seite 34

Notes4 MS-2/MS-4 PN 51512:E 01/18/05

Seite 35

Operating Instructions Status LEDs40 MS-2/MS-4 PN 51512:E 01/18/05Silent WalktestTo perform a silent Walktest, press the Walktest button, then pres

Seite 36

Operation Operating InstructionsMS-2/MS-4 PN 51512:E 01/18/05 41Zone Supervisory LEDA yellow LED for each zone that blinks if the zone has been pro

Seite 37 - Gentex Synchronization OFF ON

Operating Instructions Operation42 MS-2/MS-4 PN 51512:E 01/18/054.4.1 Fire Alarm ResponseThe control panel will, upon detection of an alarm condit

Seite 38 - Operating Instructions

Operation Operating InstructionsMS-2/MS-4 PN 51512:E 01/18/05 434.4.5 Trouble Condition ResponseThe control panel, upon detection of one or more t

Seite 39 - 4.2 Walktest

Power Supply Calculations Overview44 MS-2/MS-4 PN 51512:E 01/18/05SECTION 5 Power Supply Calculations5.1 OverviewThis section contains instructions

Seite 40 - 4.3 Status LEDs

Calculating the System Current Draw Power Supply CalculationsMS-2/MS-4 PN 51512:E 01/18/05 455.3 Calculating the System Current Draw5.3.1 OverviewT

Seite 41 - 4.4 Operation

Power Supply Calculations Calculating the System Current Draw46 MS-2/MS-4 PN 51512:E 01/18/05Table 5-3 contains three columns for calculating curr

Seite 42 - 4.4.2 Fire Alarm Restoral

Calculating the Battery Size Power Supply CalculationsMS-2/MS-4 PN 51512:E 01/18/05 475.4 Calculating the Battery SizeUse Table 5-4 to calculate t

Seite 43

Notes48 MS-2/MS-4 PN 51512:E 01/18/05

Seite 44 - 5.1 Overview

MS-2/MS-4 PN 51512:E 01/18/05 49IndexNumerics2 Zone Main Circuit Board 84 Zone M

Seite 45 - 5.3.1 Overview

MS-2/MS-4 P/N: 51512:E 01/18/05

Seite 46

50 MS-2/MS-4 PN 51512:E 01/18/05IndexEEarth Fault LED 41earth ground 19enablesee also zone enable/disable 11End-of-Line resistorIDC 12, 20, 21NAC

Seite 47

MS-2/MS-4 PN 51512:E 01/18/05 51Indexcurrent 22disable 36End-of-Line resistor 12

Seite 48

52 MS-2/MS-4 PN 51512:E 01/18/05Indexcontact rating 12fail-safe 23trouble reminder 34trouble response 43trouble restoral 43UULwiring requirements

Seite 49

NotesMS-2/MS-4 PN 51512:E 01/18/05 53

Seite 50

Notes54 MS-2/MS-4 PN 51512:E 01/18/05

Seite 51

LimWarLg.p65 01/10/2000The manufacturer warrants its products to be free from defects in materials and workmanshipfor eighteen (18) months from the

Seite 52

World HeadquartersOne Fire-Lite Place, Northford, CT 06472-1653 USA203-484-7161 • Fax 203-484-7118www.firelite.com©2005 by Honeywell International I

Seite 53

Table of Contents6 M

Seite 54

MS-2/MS-4 PN 51512:E 01/18/05 7It is imperative that the installer understand the requirements of the Authority Having Jurisdiction (AHJ) and be fa

Seite 55 - LimWarLg.p65 01/10/2000

8 MS-2/MS-4 PN 51512:E 01/18/05 MS-2(E) Main Circuit BoardJ7 Transformer Connector120 VAC, 2.3A or220/240 VAC, 1.15AE

Seite 56 - World Headquarters

MS-2/MS-4 PN 51512:E 01/18/05 9MS-4(E) Main Circuit BoardON12345678ON12345678ON12345678SUPERVISORYSUPERVISORYSUPERVISORYSUPERVISORYTROUBLETROUBLETR