PRODUCT DATA
60-2309-13
V4055A,B,D,E
On-Off Fluid Power Gas
Valve Actuator
APPLICATION
The V4055 Gas Valve Actuator, in combination with a
VE5000
a
, V5055 or V5097 Gas Valve, controls the gas supply
to commercial and industrial burners.
When replacing a V4034 with a V4055, the V5034 gas valve
must also be replaced with a V5055 or V5097 gas valve.
FEATURES
The V4055 Actuator, when used with the VE5000
a
,
V5097 or V5055 Valve, is rated for final safety shutoff
service.
The V4055 Actuator can be used with the characterized
guide model of the V5055 or V5097 Gas Valve to
enhance lightoff smoothness.
The standard model has an opening time of 26
seconds at 60 Hz or 32 seconds at 50 Hz. A fast-
opening model is available with timings of 13 seconds
at 60 Hz or 16 seconds at 50 Hz.
Maximum closing time is one second, which meets
code, standard and insurer requirements.
Models available with damper shaft, with or without
spring return; shaft extends out both sides and rides in
Teflon-like Delrin bushings; used with standard
7616BR Damper Crank Arm.
Red OPEN indicator attached to actuator stem shows
when valve is even slightly open; yellow SHUT
indicator on valve stem shows only when gas valve is
fully closed.
Models available with adjustable max flow limit switch.
Ambient temperature rating is -40°F to +150°F (-40°C to
+66°C) for 60 Hz models and -10°F to +158°F (-23°C to
+70°C) for 50 Hz and 50/60 Hz models.
Valve and actuator combinations can be mounted in
any position, with the exception of the 220 to 240 Vac,
50/60 Hz models, which are mounted vertically.
Models available with factory-installed single pole
double throw (spdt) field-adjustable Auxiliary Switch.
Field-addable Auxiliary Switch kits are also available.
Standard enclosure meets NEMA 1 (IP30)
requirements; models available with NEMA 4 (IP54)
weatherproof enclosure.
V4055D and high pressure V4055E with Proof-of-
Closure Switch and V5055/V5097C or E with valve seal
overtravel interlock (double seal) to meet specific
code, standard and insurer requirements.
a
VE5000 is a European manufactured and approved valve for
European use only.
Contents
Application ........................................................................ 1
Features ........................................................................... 1
Specifications ................................................................... 2
Ordering Information ........................................................ 2
Installation ........................................................................ 4
Wiring ............................................................................... 6
Checkout and Service ...................................................... 7
Seitenansicht 0
1 2 3 4 5 6 7 8

Inhaltsverzeichnis

Seite 1 - Valve Actuator

PRODUCT DATA60-2309-13V4055A,B,D,EOn-Off Fluid Power Gas Valve ActuatorAPPLICATIONThe V4055 Gas Valve Actuator, in combination with a VE5000a, V5055 o

Seite 2 - SPECIFICATIONS

V4055A,B,D,E ON-OFF FLUID POWER GAS VALVE ACTUATOR60-2309—13 2ORDERING INFORMATIONWhen purchasing replacement and modernization products from your TRA

Seite 3 - 3 60-2309—13

V4055A,B,D,E ON-OFF FLUID POWER GAS VALVE ACTUATOR3 60-2309—13Table 3. V4055A,D Electrical Ratings.a 50 Hz power supply.b 60 Hz power supply.c 230 Vac

Seite 4 - INSTALLATION

V4055A,B,D,E ON-OFF FLUID POWER GAS VALVE ACTUATOR60-2309—13 4Accessories:133568 Auxiliary Switch Bag Assembly (not for models with maximum flow limit

Seite 5 - 5 60-2309—13

V4055A,B,D,E ON-OFF FLUID POWER GAS VALVE ACTUATOR5 60-2309—13IMPORTANT1. All wiring must comply with all applicable electrical codes, ordinances, and

Seite 6 - 60-2309—13 6

V4055A,B,D,E ON-OFF FLUID POWER GAS VALVE ACTUATOR60-2309—13 6Fig. 3. 7616BR Damper Crank Arm can be attached to actuator shaft to drive a damper when

Seite 7 - CHECKOUT AND SERVICE

V4055A,B,D,E ON-OFF FLUID POWER GAS VALVE ACTUATOR7 60-2309—13CHECKOUT AND SERVICECAUTIONEquipment Damage Hazard.Unskilled technicians can cause equip

Seite 8 - Printed in U.S.A

V4055A,B,D,E ON-OFF FLUID POWER GAS VALVE ACTUATORAutomation and Control SolutionsHoneywell International Inc.1985 Douglas Drive NorthGolden Valley, M