Troubleshooting (Continued)
1 Applicable to heating-cooling subbase only.
Problem Check Action
Burner-on time too
short.
anticipator setting. (See Fig. 6
for anticipator location.)
Increase anticipator setting by 0.05. Observe
burner operation.
Burner-on time too
long.
anticipator setting. (See Fig. 6
for anticipator location.)
Decrease anticipator setting by 0.05. Observe
burner operation.
No cooling. system switch. May be in OFF
or HEAT position. 1
Move switch to COOL position.
fuse or circuit breaker. If fuse is blown or breaker tripped, replace or
reset.
condenser switch position.
Located outdoors and may be
turned Off.
Move to ON position.
Continued