PRODUCT DATA
C645A-E
Pressure Switches
FEATURES
C645A,B models are for use on natural gas, LP gas,
or air.
C645B1047 includes a scaleplate stop to meet
American Gas Association (AGA) requirements for
gas-fired boilers with inputs over 2-1/2 million Btuh.
C645C,D models are for use on air only.
C645E for use with distillate fuel oil.
Spring-loaded diaphragm actuates snap-acting
Micro Switch.
Switch can be wired to turn on alarm.
C645A,C and D models break control circuit on
pressure fall.
C645B models break control circuit on pressure rise.
Lockout and manual reset optional in A and C models.
Removable, zinc-plated cover protects scaleplate and
adjusting screw.
Lockout models have external manual reset lever.
Pipe tappings allow selection of positive pressure,
differential-pressure, or venting connections.
Optional switch position indicator available.
Models of C645A,B available with cover window for
setpoint visibility.
Buna-N fiber-reinforced material for increased control
diaphragm strength.
Two seal-off diaphragms for added reliability.
60-2159-8
C645A,B with Window
GENERAL
The C645 pressure switches are safety devices used in
positive-pressure or differential-pressure systems to sense
gas or air pressure changes.
C645A,B,D,E
C645C
Contents
General ............................................................................... 1
Features .............................................................................. 1
Specifications ...................................................................... 2
Ordering Information ........................................................... 2
Installation ........................................................................... 4
Settings and Adjustments ................................................... 6
Operation and Checkout ..................................................... 7
Seitenansicht 0
1 2 3 4 5 6 7 8

Inhaltsverzeichnis

Seite 1 - Pressure Switches

Copyright © 1995 Honeywell Inc. • All Rights ReservedPRODUCT DATAC645A-EPressure SwitchesFEATURES• C645A,B models are for use on natural gas, LP g

Seite 2 - ORDERING INFORMATION

60-2159—82C645A-E PRESSURE SWITCHESSPECIFICATIONSModels:C645A,C,D Pressure Switches—break a circuit whenpressure falls to scale setting minus the diff

Seite 3 - C645A-E PRESSURE SWITCHES

60-2159—83C645A-E PRESSURE SWITCHESSwitching:Spdt Micro Switch snap-acting switch (Fig. 3).Minimum Ambient Temperature:-20°F (- 29°C).Maximum Ambient

Seite 4 - INSTALLATION

60-2159—84C645A-E PRESSURE SWITCHES5(127)3-5/8(92)1-13/16(46)5/16(7.9)1(25.4)3/4(19)2-1/4(57.1)2-3/4(69.8)1-1/4(31.7)2-5/8(66.7)3/4(19)3(76.2)3-7/8(98

Seite 5

60-2159—85C645A-E PRESSURE SWITCHESThe C645E1002 Distillate Fuel Oil Pressure Switch is thesame as the C645A1006 Gas Pressure Switch except that itdoe

Seite 6 - SETTINGS AND ADJUSTMENTS

60-2159—86C645A-E PRESSURE SWITCHESSETTINGS AND ADJUSTMENTSPressure Setpoint AdjustmentTables 2 through 4 give the pressure and switching for eachsetp

Seite 7 - OPERATION AND CHECKOUT

60-2159—87C645A-E PRESSURE SWITCHESThe C645B spring-loaded diaphragm actuates the MicroSwitch snap-acting switch which breaks a control circuit, locks

Seite 8

60-2159—88C645A-E PRESSURE SWITCHESHome and Building ControlHoneywell Inc.1985 Douglas Drive NorthGolden Valley, Minnesota 55422Home and Building Cont